       Unistrut P2000 & 4000
Support Systems
           T=14mm x 28mm
41
41
A = /m = I y-y = Z y-y = r y-y = I z-z = Z z-z = r z-z =
1.92 cm2 1.72 kg/m 4.24 cm4 2.04 cm3 1.48 cm 6.10 cm4 2.95 cm3 1.78 cm
T= 11 x 25 mm
           50
1.5mm
      P2000T
PO
PG
HG
    L(mm)
                         Fmax(kN)
F
σ=175 N/mm2
f
fmax(mm)
  f=1/ 200 L
  f=1/ 360 L
     F(kN)
   F (kN)
  F (kN)
   250 500 750 1000 1250 1500 1750 2000 2250 2500 2750 3000
                       11.42 0.26 -- 5.71 1.06 --
3.81 2.40 2.85 4.27 2.28 6.68 1.90 9.62 1.63 13.10 1.42 17.11 1.27 21.65 1.14 26.73 1.03 32.35 0.95 38.50
- 3.30 *- 1.85 2.13 1.18 1.48 0.82 1.09 0.60 0.83 0.46 0.66 0.36 0.53 0.29 0.43 0.24 0.36 0.21
   11.35 10.87 10.65 9.30 7.79 6.54 5.55 4.78 4.17 3.69 3.30* 3.05*
                          * K. L / r = >180< 250
        T= 11 x 25 mm
41 21
1.5mm
A = /m = I y-y = Z y-y = r y-y = I z-z = Z z-z = r z-z =
1.34 cm2 1.16 kg/m 0.78 cm4 0.71 cm3 0.76 cm 3.66 cm4 1.77 cm3 1.65 cm
                      50
  P4000T10
PG
  L(mm)
                   Fmax(kN)
F
σ=175 N/mm2
f
fmax(mm)
  f=1/ 200 L
  f=1/ 360 L
    F(kN)
  F (kN)
  F (kN)
   250 500 750 1000 1250 1500 1750 2000
               3.976 1.988 1.325 0.994 0.795 0.663 0.568 0.497
0.51 - -
2.02 4.55 8.09 12.65 18.21 24.79 32.38
- 1.092 0.614 0.393 0.273 -
-
1.364 0.606 0.341 0.218 -
- -
   - - - - - - - -
                   Part No.
 Length M
  Finish
 3
6
PO
PG
 HG
  P2000T • • • • • P4000T10 • • •